Ground Master® Monitor
dpvlink 16954
Application example: monitoring of assembly tool
Many assembly tools consist of several parts which are not always grounded. Their ground connection may also be broken during maintenance, modifications and even in normal use. Ground Master® can monitor ground connection of every single part of the entire tool to assure its compliance with the standards and uninterrupted operation of the tool. Ground Master® RT can provide relay closure or logic level signal to the tool to stop in case of ground failure.
Many assembly tools consist of several parts which are not always grounded. Their ground connection may also be broken during maintenance, modifications and even in normal use. Ground Master® can monitor ground connection of every single part of the entire tool to assure its compliance with the standards and uninterrupted operation of the tool. Ground Master® RT can provide relay closure or logic level signal to the tool to stop in case of ground failure.
Ordering information
Ground Master comes with:
- four spare fuses
- grounding hardware
- universal power adapter
- user manual
Please contact us for further options and accessories.
Key advantages
- ANSI/ESDA S.20.20 compliant
Ground Master measures ground impedance in accordance with requirements of ANSI/ESDA S.20.20 standard - Adjustable alarm threshold
The alarm threshold can be easily adjusted at any time in a range of 1 to 20 Ohms - Safety
Each ground connection is protected by individual fuses to protect equipment in case of miswiring of neutral, power and ground - EMI
Ground Master monitors EMI on each ground and indicates EMI status - Output to Data Aquisition or Facility Monitoring System
Ground Master monitors provide intelligent output to a data acquisition or facility monitoring system. Power can be supplied via the same cable from FMS as well - Output to the Tool
Ground Master RT provides relay closure and logic signal to the tool to shut it down when any of the grounds fail
Technical data
Ground impedance
Display
Other
Connections
Ground Master ist available with two different interfaces:
General
Alarm threshold | 1 ... 20 Ohm (adjustable by the user) |
EMI on ground | 0dBm broadband |
Display
Visual | LEDs for each channel |
Audio | Buzzer |
Other
Enable switches | each channel |
Connections
Relay output with RT models | N/C relay contacts, logic level output via plug connector |
1. Current interface for FMS, DAQ | 4 … 20 mA RJ45 connector |
2. MODBUS interface (for SMP) | MODBUS compliant, RJ45 connector |
General
Power supply (local or network) | |
Voltage | 24V DC |
Power consumption | < 250mA |
Dimensions (without mounting bracket) | 114 x 92 x 28 mm |
Applications
|
|
|
|
|
|
|
|
|
|
|
|
|
|
- Permanent ground monitoring
- ANSI-ESDA S.20.20 compliant
- Adjustable alarm threshold
- EMI monitoring on each ground connection
- Safety protection for each ground connection
- Enable switches for each ground connection
- Industrial network interface
- Connection to a Facility Monitoring System
- With RT model relay and logic level output
Article image
Article description
ESD
Recommended calibration interval
Voltage
Height
Length
Width
Weight
Price
Compare
12 months bzw. according to test equipment list
100 - 240 V
30 mm
90 mm
140 mm
0.18 kg